Try searching by key words, order- or product code or serial number e.g. “CM442” or “Technical information”
Enter at least 2 characters to start the search.
Liquipoint FTW31 - Conductive point level detection

Conductive
Point level detection
Liquipoint FTW31

Rod probe for multipoint detection for up to 5 switch points

FTW31
Please Wait (spinning wheel)
Loading price
Prices temporarily unavailable
Price on request
activating price
price: provide information
from CHF ??.-
Filter Measuring / Application task
Measuring / Application task

Configure to download the CAD drawings of this product

  • Measuring principle

    Conductive

  • Characteristic / Application

    Compact rod probe with multipoint detection, possible up to 5 switch points. Simple rod shortening.

  • Supply / Communication

    DC PNP 10,8V ... 45V
    Relay 20V ... 230V AC
    Relay 20V ... 55V DC

  • Ambient temperature

    -40 °C ... 70 °C
    (-40 °F ... 158 °F)

  • Process temperature

    -40 °C ... 100 °C
    (-40 °F ... 212 °F)

  • Process pressure / max. overpressure limit

    Vacuum ... 10 bar
    (Vacuum ... 145 psi)

  • Min. conductivity of medium

    10 µS/cm

  • Main wetted parts

    316L, PP, PPS

  • Max. tensile strength

    1000 N

  • Process connection

    G 1 1/2
    NPT1 1/2"

  • Sensor length

    0.1m ... 4m
    (3.9" ... 157")

  • Communication

    DC PNP
    Relay

  • Certificates / Approvals

    ATEX, EAC Ex

  • Safety approvals

    Leakage Detection

  • Components

    Transmitter: FTW325

  • Application limits

    Observe min. medium conductivity